PICS 0 BACnet Protocol Implementation Conformance Statement -- -- -- Generated by BACnet Protocol Stack library EPICS tool -- BACnet/IP Interface for BACnet-stack Devices -- http://sourceforge.net/projects/bacnet/ -- -- Vendor Name: "DAIKIN Industries LTD" Product Name: "D-BACS BACnet Gateway" Product Model Number: "D-BACS BACnet Gateway" Product Description: "your product description here" BIBBs Supported: { DS-RP-B -- possible BIBBs in this device -- DS-RPM-B -- DS-WP-B -- DM-DDB-B -- DM-DOB-B -- DM-DCC-B -- DM-RD-B -- DS-COV-A -- DS-COV-B -- AE-N-A -- AE-N-I-B -- AE-N-E-B -- AE-ACK-B -- AE-ACK-A -- DM-UTC-B } BACnet Standard Application Services Supported: { -- services reported by this device Subscribe-COV Add-List-Element Remove-List-Element Read-Property Read-Property-Multiple Write-Property Write-Property-Multiple Device-Communication-Control I-Am Time-Synchronization Who-Has Who-Is UTC-Time-Synchronization } Standard Object-Types Supported: { -- objects reported by this device analog-input analog-value binary-input binary-output binary-value device multi-state-input multi-state-output notification-class accumulator } Data Link Layer Option: { -- choose the data link options supported -- ISO 8802-3, 10BASE5 -- ISO 8802-3, 10BASE2 -- ISO 8802-3, 10BASET -- ISO 8802-3, fiber -- ARCNET, coax star -- ARCNET, coax bus -- ARCNET, twisted pair star -- ARCNET, twisted pair bus -- ARCNET, fiber star -- ARCNET, twisted pair, EIA-485, Baud rate(s): 156000 -- MS/TP master. Baud rate(s): 9600, 38400 -- MS/TP slave. Baud rate(s): 9600, 38400 -- Point-To-Point. EIA 232, Baud rate(s): 9600 -- Point-To-Point. Modem, Baud rate(s): 9600 -- Point-To-Point. Modem, Baud rate(s): 9600 to 115200 -- BACnet/IP, 'DIX' Ethernet -- BACnet/IP, Other -- Other } Character Sets Supported: { -- choose any character sets supported -- ANSI X3.4 -- IBM/Microsoft DBCS -- JIS C 6226 -- ISO 8859-1 -- ISO 10646 (UCS-4) -- ISO 10646 (UCS2) } Special Functionality: { Maximum APDU size in octets: 1024 } List of Objects in Test Device: { { object-identifier: (device, 1) object-name: "DAIKIN MasterStation III No 1" object-type: device system-status: operational vendor-name: "DAIKIN Industries LTD" vendor-identifier: 53 model-name: "D-BACS BACnet Gateway" firmware-revision: "Ver.000.001" application-software-version: "06_30_00" protocol-version: 1 protocol-revision: 4 protocol-services-supported: ( F,F,F,F, -- ,,,, F,T,F,F, -- , Subscribe-COV,,, T,T,F,F, -- Add-List-Element, Remove-List-Element,,, T,F,T,T, -- Read-Property,, Read-Property-Multiple, Write-Property, T,T,F,F, -- Write-Property-Multiple, Device-Communication-Control,,, F,F,F,F, -- ,,,, F,F,T,F, -- ,, I-Am,, F,F,F,F, -- ,,,, T,T,T,F, -- Time-Synchronization, Who-Has, Who-Is,, T,F,F,F -- UTC-Time-Synchronization,,,, ) protocol-object-types-supported: ( T,F,T,T, -- analog-input,, analog-value, binary-input, T,T,F,F, -- binary-output, binary-value,,, T,F,F,F, -- device,,,, F,T,T,T, -- , multi-state-input, multi-state-output, notification-class, F,F,F,F, -- ,,,, F,F,F,T, -- ,,, accumulator, F -- , ) object-list: { (device, 1), (notification-class, 3), (binary-output, 1), (binary-input, 2), (binary-input, 3), (multi-state-input, 4), (multi-state-output, 5), (multi-state-input, 6), (multi-state-output, 7), (multi-state-input, 8), (analog-input, 9), (analog-value, 10), (binary-input, 11), (binary-value, 12), (binary-value, 13), (binary-value, 14), (binary-value, 16), (accumulator, 18), (accumulator, 19), (binary-input, 20), (analog-value, 22), (analog-input, 23), (binary-output, 24), (binary-input, 25), (binary-output, 26), (binary-input, 27), (binary-input, 28), (binary-input, 29), (binary-input, 30), (binary-input, 31), (binary-value, 17), (binary-value, 21), (binary-value, 16401), (binary-value, 16405) } max-apdu-length-accepted: 1024 segmentation-supported: segmented-both apdu-timeout: 6000 number-of-APDU-retries: 3 device-address-binding: ? database-revision: ? max-segments-accepted: 100 local-time: ? local-date: ? utc-offset: ? daylight-savings-status: ? apdu-segment-timeout: 6000 active-cov-subscriptions: Null -- Found 34 Objects }, { object-identifier: (analog-input, 9) object-name: "RoomTemp_000" object-type: analog-input present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE units: degrees-celsius }, { object-identifier: (analog-input, 23) object-name: "AirDirectionStatus_000" object-type: analog-input present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE units: no-units reliability: ? COV-increment: 1.000000 }, { object-identifier: (analog-value, 10) object-name: "TempAdjust_000" object-type: analog-value present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE units: degrees-celsius reliability: ? priority-array: ? relinquish-default: 25.000000 COV-increment: 1.000000 }, { object-identifier: (analog-value, 22) object-name: "AirDirectionCommand_000" object-type: analog-value present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE units: no-units reliability: ? priority-array: ? relinquish-default: 0.000000 COV-increment: 1.000000 }, { object-identifier: (binary-input, 2) object-name: "StartStopStatus_000" object-type: binary-input present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE polarity: normal reliability: ? change-of-state-time: { Monday, July 15, 2024,14:55:18.00 } change-of-state-count: 170 time-of-state-count-reset: { any day of week, Any Month (unspecified), (unspecified),**:**:**.** } elapsed-active-time: 156749100 time-of-active-time-reset: { any day of week, Any Month (unspecified), (unspecified),**:**:**.** } }, { object-identifier: (binary-input, 3) object-name: "Alarm_000" object-type: binary-input present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE polarity: normal }, { object-identifier: (binary-input, 11) object-name: "FilterSign_000" object-type: binary-input present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE polarity: normal }, { object-identifier: (binary-input, 20) object-name: "CommunicationStatus_000" object-type: binary-input present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE polarity: normal }, { object-identifier: (binary-input, 25) object-name: "ForcedThermoOFFStatus_000" object-type: binary-input present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE polarity: normal reliability: ? }, { object-identifier: (binary-input, 27) object-name: "EnergyEfficiencyStatus_000" object-type: binary-input present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE polarity: normal reliability: ? }, { object-identifier: (binary-input, 28) object-name: "ThermoStatus_000" object-type: binary-input present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE polarity: normal reliability: ? }, { object-identifier: (binary-input, 29) object-name: "CompressorStatus_000" object-type: binary-input present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE polarity: normal reliability: ? }, { object-identifier: (binary-input, 30) object-name: "IndoorFanStatus_000" object-type: binary-input present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE polarity: normal reliability: ? }, { object-identifier: (binary-input, 31) object-name: "HeaterStatus_000" object-type: binary-input present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE polarity: normal reliability: ? }, { object-identifier: (binary-output, 1) object-name: "StartStopCommand_000" object-type: binary-output present-value: ? Writable status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE polarity: normal priority-array: ? relinquish-default: inactive reliability: ? }, { object-identifier: (binary-output, 24) object-name: "ForcedThermoOFFCommand_000" object-type: binary-output present-value: ? Writable status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE polarity: normal priority-array: ? relinquish-default: inactive reliability: ? }, { object-identifier: (binary-output, 26) object-name: "EnergyEfficiencyCommand_000" object-type: binary-output present-value: ? Writable status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE polarity: normal priority-array: ? relinquish-default: inactive reliability: ? }, { object-identifier: (binary-value, 12) object-name: "FilterSignReset_000" object-type: binary-value present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE }, { object-identifier: (binary-value, 13) object-name: "RemoteControlStart_000" object-type: binary-value present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE reliability: ? priority-array: ? relinquish-default: inactive }, { object-identifier: (binary-value, 14) object-name: "RemoteControlAirConModeSet_000" object-type: binary-value present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE reliability: ? priority-array: ? relinquish-default: inactive }, { object-identifier: (binary-value, 16) object-name: "RemoteControlTempAdjust_000" object-type: binary-value present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE reliability: ? priority-array: ? relinquish-default: inactive }, { object-identifier: (binary-value, 17) object-name: "CL_Rejection_000" object-type: binary-value present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE reliability: ? priority-array: ? relinquish-default: inactive }, { object-identifier: (binary-value, 21) object-name: "SystemForcedOff_000" object-type: binary-value present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE reliability: ? priority-array: ? relinquish-default: inactive }, { object-identifier: (binary-value, 16401) object-name: "CL_Rejection_064" object-type: binary-value present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE reliability: ? priority-array: ? relinquish-default: inactive }, { object-identifier: (binary-value, 16405) object-name: "SystemForcedOff_064" object-type: binary-value present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE reliability: ? priority-array: ? relinquish-default: inactive }, { object-identifier: (multi-state-input, 4) object-name: "MalfunctionCode_000" object-type: multi-state-input present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE number-of-states: 512 description: "00" reliability: ? }, { object-identifier: (multi-state-input, 6) object-name: "AirConModeStatus_000" object-type: multi-state-input present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE number-of-states: 5 reliability: ? }, { object-identifier: (multi-state-input, 8) object-name: "AirFlowRateStatus_000" object-type: multi-state-input present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE number-of-states: 4 reliability: ? }, { object-identifier: (multi-state-output, 5) object-name: "AirConModeCommand_000" object-type: multi-state-output present-value: ? Writable status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE number-of-states: 5 priority-array: ? relinquish-default: 1 reliability: ? }, { object-identifier: (multi-state-output, 7) object-name: "AirFlowRateCommand_000" object-type: multi-state-output present-value: ? Writable status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE number-of-states: 4 priority-array: ? relinquish-default: 1 reliability: ? }, { object-identifier: (notification-class, 3) object-name: "Intrinsic Report Notification" object-type: notification-class notification-class: 3 priority: { 255,255,255 } ack-required: {false,false,false} recipient-list: Null }, { object-identifier: (accumulator, 18) object-name: "GasTotalPower_000" object-type: accumulator present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE scale: units: cubic-meters max-pres-value: 999999 reliability: ? }, { object-identifier: (accumulator, 19) object-name: "ElecTotalPower_000" object-type: accumulator present-value: ? status-flags: {false,false,false,false} event-state: normal out-of-service: FALSE scale: units: kilowatt-hours max-pres-value: 999999 reliability: ? } } End of BACnet Protocol Implementation Conformance Statement